Positioning of the Evaporator unit of a split type air conditioner

When positioning the evaporator unit, follow these recommendations:

- Carefully plan the location of the evaporator in order to avoid
any interference with any type of existing or projected installation, such as electrical, water, sewage, etc. installations;
- The chosen location allows the passage of the interconnection pipes as well as electrical wiring;
- Avoid proximity to electronic devices (minimum 1 m); The evaporator should be installed where there are no obstacles to the airflow (inlet and outlet).
Observe the minimum recommended distances of walls, ceiling and floor;
In the case of the type evaporators Hi Wall, pipe interconnection can go out to any of the directions shown in the figure below, but you must be very careful when bending it to avoid breakage or kneading;
- For Hi Wall evaporators, use the mounting bracket that comes with the equipment, as well as the indications for positioning the hole where it will go
passing the interconnection pipe;
- The evaporator should be leveled as the
condensate is made by gravity (with the exception of cassette-type equipment);
- In the evaporators of the cassette type, which have condensate pump,
respect the limit of manometric height that the pump has; After reaching height
pipe shall have a slope of 2% in the direction of the exit point of the water;
- For installations with more than one evaporator cassette on the same network drain, make sure the water can follow a continuous flow towards the exit point, preventing the pumped water from an evaporator will not get another evaporator;
- Ensure easy access for maintenance; Special attention on equipment of the type
Built In, which, due to the fact that they are built-in, must have a window of
inspection to enable preventive maintenance (filter cleaning) and corrective maintenance when necessary.