Unit operates continuously but with low performance of the multi-split II type air conditioner

 Insufficient refrigerant supply to the evaporator:

- Check the filter drier, distributor or lines for obstruction. Replace or correct.

- Check the expansion valve for obstruction. Replace if necessary.

- Check that the expansion valve overheats (4 to 6 ° C). Adjust if necessary.

- Check for excessive pressure loss in the refrigerant lines due to the distance, unevenness or diameter of the pipes. Correct if necessary

- Check the position of the bulb and equalizer tube of the expansion valve. Correct according to factory specification.