Reduced suction pressure of the multi-split air conditioner

 Reversal of rotation in the evaporator fan: - Check and correct

- Reduced discharge pressure.

Insufficient thermal load: Check design conditions.

- Lack of refrigerant: Check and correct leaks. Add soda

if necessary.

- Low air flow in the evaporator: Check the air filters for dirt. Clean or replace.

- Check the coil for dirt: Clean and provide adequate filtration.

- Check pipeline network regulation records.

- Check engine operation: Replace if necessary.

- Insufficient refrigerant supply: Check the filter drier, evaporator distributor or lines for obstruction. Replace if necessary.

- Check the expansion valve for obstruction. Replace if necessary.

- Check the expansion valve overheat setting (4 to 6 ° C). Adjust if necessary.

- Check for excessive pressure loss in the refrigerant lines due to the distance, unevenness or diameter of the pipes. Correct if necessary.

- Check the position of the bulb and equalizer tube of the expansion valve. Correct according to factory specification.

- Low pressure switch tripped: - Check regulation and operation.

apparent cause. Replace if necessary.