DETECTING - COMPRESSOR COIL RESISTANCE TEST

For this test the compressor must be cold (off for at least 2 hours), the ambient temperature should be around 25ºC and have a digital multimeter.
With the multimeter, the resistance between the C-A-M terminals is measured. The measured values must now be compared with the table, with a maximum variation of + or - 5%.
The compressor should be replaced if the measurements are outside the tolerance range, or the multimeter indicates infinite, which means the coil is open.