The starter relay contacts deteriorate quickly and stick together. Commercial refrigeration I

The number of hourly compressor interventions is very high (more than five).
Differential thermostat very and limited.
Replace the thermostat with another wider differential or apply the thermostat with an adjustable differential. If necessary, adjust the sensitive element of the existing thermostat, so as not to exceed five daily interventions.