The single-phase zombie compressor continues, but does not break the overload protector intervenes VIII

Overloaded refrigerant unit.
Discharge the excess refrigerant fluid very slowly from a place on the unit where there is only gas. In the case of an airtight system without registration. Use a drill register applied to the compressor service tube. Measure the load using the liquid flow indicator. If this is not installed, the same survey can be done using an ultrasound liquid flow indicator, applied temporarily at the beginning of the liquid line.