Check List for Retrofit of Systems with CFC or HCFC

 1- Determine the performance of the equipment with the existing refrigerant.

• Use the System Information Sheet provided below.

• Note the type of oil used and the operating data of the system (if the system is operating properly). • Check for leaks and repair.

 2. Remove the refrigerant charge in the system. (A 10 to 15 inch Hg vacuum [50 to 67 kPa] is required to remove the load.)

• Use a recovery cylinder (DO NOT drain into the atmosphere).

• Weigh the amount of refrigerant removed (if possible):

• Eliminate the vacuum with dry nitrogen.

 3. Replace the dryer filter.

• Check the elastomer seals (filter rings, sight glasses, etc.).

• Check that the oil is in good condition. Replace if necessary.

 4. Evacuate the system and check for leaks.

• Does the system maintain a vacuum?

• Eliminate the vacuum with dry nitrogen, pressurize to a pressure below the design pressure of the system.

• Does the system maintain pressure?

• Check for any leaks.

5. Charge the system with refrigerant

 • Remove the charge from the refrigerant only in the liquid phase of the cylinder.

 • The initial charge should be approximately 85% of the standard R-22 charge. The final load will be approximately 95%

 6. Adjust the refrigerant charge to obtain the same superheat as the original system. If the adjustment is not adequate, replace the TXV hole. (TXV: expansion valve)

7. Monitor the compressor oil levels. If necessary, add additional oil to reach the normal Operation level (middle of the display).

• If there is a sudden variation in the oil level (eg during or shortly after thawing), remove a small amount (approximately 10%) of the mineral oil and replace with POE. Repeat if necessary.

• If the oil level falls below the minimum, top up the oil to the minimum level with the type of oil available.

• If the oil level drops continuously or if large fluctuations occur during operation, add a sufficient amount of equivalent POE until the return oil is normal.

8. Clearly identify the system. Ensure that the System Information Sheet is completed and filed in a safe place.

 Retrofit is complete!