Installation of the multi-modular type air conditioner condenser unit

 If the air conditioner is installed incorrectly, it can cause accidents due to falls.

1. Place the connected external units with spaces of 20mm or more. Secure the outdoor unit with M12 anchor bolts (4 positions / unit).

The length of the appropriate anchor rod is 20mm.

2. When driving the refrigerant pipe from the bottom, adopt a floating base (floatplane) with a height of 500mm or more.

3. Do not use separate bases on the four corners.

4. Install the rubber vibration isolator so that it is received with the fixing legs of the outdoor unit.

In snowy areas, take the following precautions against snow on the outdoor unit. (Incomplete snowproof measures cause problems). Place a tall stool under the unit and mount the snow covers on the suction and discharge ports so that snow does not influence.

5. Be careful to connect the inverter and fixed speed unit.

(1) Be sure to use an inverter unit for the external unit to be connected to the main pipe.

(2) The T-junction joint, which is sold separately, can be connected to the main pipe inside the pipe indicated with a bold line.

(3) Be careful to direct the T-joint, the T-joint cannot be attached so that the main pipe refrigerant flows directly to the inverter unit).